Siemens HMI Replacement: 6AV legacy → Comfort → Unified

Siemens has published formal migration paths across several SIMATIC HMI generations — older TP/OP/MP 177/277 panels migrated to SIMATIC Comfort Panels, and Comfort Panels are now themselves migrating to SIMATIC Unified Comfort Panels. Successor hardware and project migration are two separate questions; this guide covers both.

Siemens HMI touch panel - ElecBridge
Quick Answer

Siemens has published formal migration paths across several SIMATIC HMI generations. Older TP/OP/MP 177/277 panels were migrated to SIMATIC Comfort Panels, and Siemens now identifies SIMATIC Unified Comfort Panels as the suitable successor generation for the 6AV2124 Comfort Panel family. Successor does not mean zero-engineering swap. HMI replacement usually involves two separate questions: which hardware is the Siemens successor, and how the existing HMI project is migrated. Mounting cutout, communication, software generation, screen resolution, scripts, recipes, alarms and PLC integration must all be checked before ordering.

LIFECYCLE STATUS

Current direction — Comfort to Unified

On January 31, 2026, Siemens announced product phase-out milestone P.M400 for the remaining SIMATIC HMI Comfort Panels. Siemens identifies SIMATIC Unified Comfort Panels as suitable successor products. The 15-inch to 22-inch Comfort devices had entered phase-out earlier, while the remaining 4-inch to 12-inch models reached P.M400 in January 2026.

Procurement implication

For a failed 6AV2124 Comfort Panel, the decision is no longer simply "buy the same panel or upgrade." First check exact legacy availability and project urgency; for planned modernization, use Siemens' Unified Comfort migration path and assess the engineering work.

OFFICIAL SUCCESSORS

Comfort Panel → Unified Comfort families

Comfort PanelLegacy article no.Unified successorSuccessor family pattern
KTP400 Comfort6AV2124-2DC01-0AX0MTP700 Unified Comfort6AV2128-3GB.6-0AX1
TP700 Comfort6AV2124-0GC01-0AX0MTP700 Unified Comfort6AV2128-3GB.6-0AX1
KP700 Comfort6AV2124-1GC01-0AX0MTP700 Unified + external key modules where needed6AV2128-3GB.6-0AX1 + KP8/KP32
TP900 Comfort6AV2124-0JC01-0AX0MTP1000 Unified Comfort6AV2128-3KB.6-0AX1
KP900 Comfort6AV2124-1JC01-0AX0MTP1000 Unified + external key modules where needed6AV2128-3KB.6-0AX1 + KP8/KP32
TP1200 Comfort6AV2124-0MC01-0AX0MTP1200 Unified Comfort6AV2128-3MB.6-0AX1
KP1200 Comfort6AV2124-1MC01-0AX0MTP1200 Unified + external key modules where needed6AV2128-3MB.6-0AX1 + KP8/KP32
TP1500 Comfort6AV2124-0QC02-0AX1 / -0AX2MTP1500 Unified Comfort6AV2128-3QB.6-0AX1
KP1500 Comfort6AV2124-1QC02-0AX1 / -0AX2MTP1500 Unified + external key modules where needed6AV2128-3QB.6-0AX1 + KP8/KP32
TP1900 Comfort6AV2124-0UC02-0AX1MTP1900 Unified Comfort6AV2128-3UB.6-0AX1
TP2200 Comfort6AV2124-0XC02-0AX1MTP2200 Unified Comfort6AV2128-3XB.6-0AX1

Siemens' phase-out announcement uses family patterns such as 6AV2128-3GB.6-0AX1 rather than one single market-neutral full order number — we preserve that pattern here rather than inventing the missing variant character; verify the exact country/variant order number with Siemens before ordering.

EARLIER GENERATION

Older 6AV6 panels → Comfort successors

Siemens' Comfort Panel delivery release and migration guide provide a clear predecessor-to-Comfort path for many widely installed 6AV6 legacy panels — these exact order numbers are high-value search terms for buyers still running them.

Legacy Siemens HMILegacy order no.Comfort successorComfort order no.
TP 177B 6" PN/DP Color6AV6642-0BA01-1AX1TP700 Comfort6AV2124-0GC01-0AX0
TP 277 6"6AV6643-0AA01-1AX0TP700 Comfort6AV2124-0GC01-0AX0
OP 277 6"6AV6643-0BA01-1AX0KP700 Comfort6AV2124-1GC01-0AX0
MP 277 8" Touch6AV6643-0CB01-1AX1TP900 Comfort6AV2124-0JC01-0AX0
MP 277 8" Key6AV6643-0DB01-1AX1KP900 Comfort6AV2124-1JC01-0AX0
MP 277 10" Touch6AV6643-0CD01-1AX1TP1200 Comfort6AV2124-0MC01-0AX0
FULL MODERNIZATION CHAIN

Two steps: legacy → Comfort → Unified

This is especially valuable for older machines, because the historically documented successor may itself now be in phase-out. A buyer searching an MP277 or TP177B needs the complete modernization chain, not only the first-generation successor.

Original modelOriginal panelHistorical Comfort successorCurrent Unified direction
6AV6642-0BA01-1AX1TP177B 6"6AV2124-0GC01-0AX0 TP700 Comfort6AV2128-3GB.6-0AX1 MTP700 Unified
6AV6643-0AA01-1AX0TP277 6"6AV2124-0GC01-0AX0 TP700 Comfort6AV2128-3GB.6-0AX1 MTP700 Unified
6AV6643-0BA01-1AX0OP277 6"6AV2124-1GC01-0AX0 KP700 Comfort6AV2128-3GB.6-0AX1 + key-module strategy
6AV6643-0CB01-1AX1MP277 8" Touch6AV2124-0JC01-0AX0 TP900 Comfort6AV2128-3KB.6-0AX1 MTP1000 Unified
6AV6643-0DB01-1AX1MP277 8" Key6AV2124-1JC01-0AX0 KP900 Comfort6AV2128-3KB.6-0AX1 + key-module strategy
6AV6643-0CD01-1AX1MP277 10" Touch6AV2124-0MC01-0AX0 TP1200 Comfort6AV2128-3MB.6-0AX1 MTP1200 Unified
MOUNTING

Cutout and mechanical compatibility

Siemens' Comfort migration guide explicitly compares mounting cutouts and enclosure dimensions. Some Comfort Panels were designed around compatible cutouts with predecessor devices, but display format, bezel size and device depth can still differ.

Comfort deviceSiemens-listed predecessor mounting familyPractical check
TP700 ComfortTP177B 6", MP177 6", TP277 6"Cutout compatibility is favorable, but verify bezel/depth and cable access
TP900 ComfortMP277 8" TouchCheck enclosure/front dimensions and internal clearance
KP900 ComfortMP277 8" KeyCheck key-panel geometry and door cutout
TP1200 ComfortMP277 10" TouchCheck cutout, bezel and internal space before ordering

For Comfort → Unified modernization, Siemens also documents mounting compatibility for several Unified Comfort sizes. Larger Unified devices may use adapter frames in some predecessor cutouts — always verify the exact current hardware manual before machining the panel door.

RISKS · PROJECT MIGRATION

Project migration is separate from hardware

Siemens explicitly separates hardware replacement from project migration

Replacing the physical HMI also requires migration of the project data. Older projects may originate in ProTool or WinCC flexible, while Comfort Panels use WinCC in TIA Portal and Unified Panels use WinCC Unified.

Comfort Panel → Unified project migration

Siemens provides a dedicated "Guide for Migrating to WinCC Unified HMI Devices" and the Data2Unified TIA Portal add-in. Siemens describes Data2Unified as a tool that can reduce migration effort — it is not a comprehensive migration tool. Use Siemens' WinCC Unified modernization guidance to assess the existing project, use Data2Unified where supported to transfer or assist with reusable content, plan manual engineering for functions that aren't converted automatically, and re-test user interaction, scripts, styles, alarms, recipes, logging and communication behavior in WinCC Unified.

Do not sell "automatic conversion"

The correct customer message: Siemens provides migration tools that reduce engineering effort, but Comfort-to-Unified modernization still requires engineering and validation.

IF THE PROJECT FILE IS MISSING

What if the original engineering project is gone

Siemens publishes separate guidance for migrating or converting certain SIMATIC HMI devices when the original engineering project is unavailable. The feasible route depends on the old device and the type of backup available — treat this as a special recovery/migration case, not something that works automatically for every panel.

COMMUNICATION

Checks before replacing a Siemens HMI

PROFIBUS/MPI warning

Do not choose a Unified Panel only by screen size if the existing machine still depends on a legacy MPI/PROFIBUS HMI connection. Confirm the controller/network architecture and the supported migration design first.

WHICH STRATEGY

Original spare, Comfort, or Unified?

StrategyWhen it may make senseMain risk
Source the exact original 6AV6 legacy panelProduction must restart immediately; editable project is unavailable; machine changes are unacceptableLegacy stock condition, authenticity, age and future availability
Use the historical 6AV2124 Comfort successorA validated Comfort migration already exists or an exact Comfort spare is requiredComfort Panels themselves are now in phase-out
Plan migration to 6AV2128 Unified ComfortLong service life and current platform support matterProject engineering, communication and operator-interface changes must be validated
HOW WE HELP

What ElecBridge checks for you

For a Siemens HMI request, we separate five questions: can the exact original 6AV model still be sourced, and what's the condition/source risk; what successor did Siemens officially publish for the original panel generation; has that successor itself entered phase-out, and what's the current Unified successor family; what engineering changes are required (project conversion, cutout, communication, key/touch operation and controller compatibility); and whether a short-term original spare or a planned modernization is economically more appropriate for you.

What to send us

Full Siemens article number beginning 6AV... · front and rear nameplate photos · screen size and touch/key operation · PLC/controller model · MPI/PROFIBUS/PROFINET/Ethernet/serial connection information · original WinCC flexible / TIA Portal project file if available · ProSave/device backup if that's all that exists · panel cutout dimensions and cabinet-door photo · required quantity and destination country.

SOURCES

Manufacturer references

Siemens — Delivery Release: SIMATIC HMI Comfort Panels, Entry ID 49727602, 5 May 2011 · Siemens — SIMATIC HMI Comfort Panels Migration Guide, Entry/manual ID 49752044 · Siemens — End of Production for SIMATIC MP 277 Panels with Narrow Frame, Entry ID 63647346 · Siemens — Status change for SIMATIC HMI products, Entry ID 109486162 · Siemens — Product phase-out announcement (P.M400): SIMATIC HMI Comfort Panels, Entry ID 109824856, 31 Jan 2026.

Technical disclaimer: ElecBridge is an independent sourcing service and is not Siemens. This page summarizes Siemens' published migration and phase-out information for practical sourcing use and must not be presented as Siemens engineering approval. Final panel selection, project migration, mounting/cutout fit, communication configuration and commissioning must be verified for the actual machine and control system.

— GET STARTED

Send your 6AV model / nameplate for a check

Tell us the full Siemens article number and application — within 48 hours you get an honest replacement judgment. Official successor path, project migration risk, and what to verify before you order.

Send your HMI details for a check
WhatsApp:+86 189 9841 9159 · [email protected]
FAQ

Siemens HMI replacement frequently asked

Q.01
What replaces Siemens MP277 10" Touch 6AV6643-0CD01-1AX1?
Siemens historically mapped MP277 10" Touch 6AV6643-0CD01-1AX1 to TP1200 Comfort 6AV2124-0MC01-0AX0. The current modernization direction moves to the MTP1200 Unified family 6AV2128-3MB.6-0AX1.
Q.02
What replaces Siemens MP277 8" Touch 6AV6643-0CB01-1AX1?
The Comfort migration guide maps it to TP900 Comfort 6AV2124-0JC01-0AX0; the current modernization direction is the MTP1000 Unified family 6AV2128-3KB.6-0AX1.
Q.03
What replaces Siemens TP277 6" 6AV6643-0AA01-1AX0?
Siemens maps TP277 6" to TP700 Comfort 6AV2124-0GC01-0AX0. The current Unified successor family for TP700 Comfort is 6AV2128-3GB.6-0AX1.
Q.04
What replaces Siemens TP177B 6AV6642-0BA01-1AX1?
The Comfort migration path leads to TP700 Comfort 6AV2124-0GC01-0AX0; current modernization then moves to the MTP700 Unified family 6AV2128-3GB.6-0AX1.
Q.05
What replaces Siemens TP700 Comfort 6AV2124-0GC01-0AX0?
Siemens' 2026 Comfort Panel phase-out announcement lists the Unified Comfort successor family 6AV2128-3GB.6-0AX1.
Q.06
What replaces Siemens TP900 Comfort 6AV2124-0JC01-0AX0?
Siemens lists the Unified Comfort successor family 6AV2128-3KB.6-0AX1.
Q.07
What replaces Siemens TP1200 Comfort 6AV2124-0MC01-0AX0?
Siemens lists the MTP1200 Unified Comfort successor family 6AV2128-3MB.6-0AX1.
Q.08
Can I restore an MP277 backup directly to a Unified Comfort Panel?
No direct claim should be made. Hardware generation and engineering software differ — the project must follow Siemens' supported migration path and be validated, not restored as a direct image.
Q.09
Can Data2Unified automatically convert a Comfort Panel project?
Siemens says Data2Unified can reduce migration effort but is not a comprehensive migration tool. Manual engineering and testing can still be required.
Q.10
Will the new Siemens HMI fit the old panel cutout?
Some successor pairs have compatible or closely related cutouts, but bezel, device depth and current Unified mounting requirements must be verified for the exact models before you cut the panel door.