For many ABB ACS550 general-purpose drive applications, ACS580 is ABB's intended migration platform — but it should never be selected by HP or kW rating alone. This guide walks through ABB's official model mappings, option/fieldbus changes and the checks worth confirming before you order.

For many ABB ACS550 general-purpose drive applications, ACS580 is the migration path ABB itself points to. But an ACS580 should never be selected only by matching the old drive's HP or kW rating. Before ordering, verify: the exact ACS550 type designation, motor power and rated current, supply voltage and duty requirement, enclosure/protection class, existing option modules and fieldbus, mechanical dimensions and mounting, and control wiring / parameter settings. ACS580 is a migration path for many ACS550 applications — not an automatic drop-in replacement.
ABB's ACS550-to-ACS580 comparison guide organizes the work into two practical stages:
| ACS550 | ACS550 current | ACS580 | ACS580 current | Typical power |
|---|---|---|---|---|
| ACS550-U1-03A3-4 | 3.3 A | ACS580-01-03A0-4 | 3.0 A | 1.5 HP |
| ACS550-U1-04A1-4 | 4.1 A | ACS580-01-03A5-4 | 3.5 A | 2 HP |
| ACS550-U1-06A9-4 | 6.9 A | ACS580-01-04A8-4 | 4.8 A | 3 HP |
| ACS550-U1-08A8-4 | 8.8 A | ACS580-01-07A6-4 | 7.6 A | 5 HP |
| ACS550-U1-012A-4 | 11.9 A | ACS580-01-012A-4 | 12 A | 7.5 HP |
| ACS550-U1-015A-4 | 15.4 A | ACS580-01-014A-4 | 14 A | 10 HP |
| ACS550-U1-023A-4 | 23 A | ACS580-01-023A-4 | 23 A | 15 HP |
| ACS550-U1-031A-4 | 31 A | ACS580-01-027A-4 | 27 A | 20 HP |
| ACS550-U1-038A-4 | 38 A | ACS580-01-034A-4 | 34 A | 25 HP |
| ACS550-U1-045A-4 | 44 A | ACS580-01-044A-4 | 44 A | 30 HP |
| ACS550-U1-059A-4 | 59 A | ACS580-01-052A-4 | 52 A | 40 HP |
| ACS550-U1-072A-4 | 72 A | ACS580-01-065A-4 | 65 A | 50 HP |
| ACS550-U1-078A-4 | 77 A | ACS580-01-077A-4 | 77 A | 60 HP |
| ACS550-U1-097A-4 | 96 A | ACS580-01-096A-4 | 96 A | 75 HP |
| ACS550-U1-125A-4 | 124 A | ACS580-01-124A-4 | 124 A | 100 HP |
| ACS550-U1-157A-4 | 157 A | ACS580-01-156A-4 | 156 A | 125 HP |
| ACS550-U1-180A-4 | 180 A | ACS580-01-180A-4 | 180 A | 150 HP |
| ACS550-U1-246A-4 | 245 A | ACS580-01-240A-4 | 240 A | 200 HP |
These are ABB comparison-guide mappings. Do not use this table as a universal one-to-one interchangeability statement. Final sizing still depends on motor current, voltage, duty, options and application.
| ACS550 | ACS580 |
|---|---|
| ACS550-U1-04A6-2 | ACS580-01-04A6-2 |
| ACS550-U1-06A6-2 | ACS580-01-06A6-2 |
| ACS550-U1-07A5-2 | ACS580-01-07A5-2 |
| ACS550-U1-012A-2 | ACS580-01-10A6-2 |
| ACS550-U1-017A-2 | ACS580-01-017A-2 |
| ACS550-U1-024A-2 | ACS580-01-024A-2 |
| ACS550-U1-031A-2 | ACS580-01-031A-2 |
| ACS550-U1-046A-2 | ACS580-01-046A-2 |
| ACS550-U1-059A-2 | ACS580-01-059A-2 |
| ACS550-U1-075A-2 | ACS580-01-075A-2 |
| ACS550-U1-088A-2 | ACS580-01-090A-2 |
| ACS550-U1-114A-2 | ACS580-01-114A-2 |
| ACS550-U1-143A-2 | ACS580-01-143A-2 |
| ACS550-U1-178A-2 | ACS580-01-169A-2 |
| ACS550-U1-221A-2 | ACS580-01-211A-2 |
| ACS550-U1-248A-2 | ACS580-01-273A-2 |
ABB states that the ACS550 208–240 V single-phase 50% output-current derating rule should not simply be applied to ACS580. Use the ACS580 single-phase selection ratings instead.
| ACS550 | ACS580 |
|---|---|
| ACS550-U1-02A7-6 | ACS580-01-02A7-6 |
| ACS550-U1-03A9-6 | ACS580-01-03A9-6 |
| ACS550-U1-06A1-6 | ACS580-01-06A1-6 |
| ACS550-U1-09A0-6 | ACS580-01-09A0-6 |
| ACS550-U1-011A-6 | ACS580-01-011A-6 |
| ACS550-U1-017A-6 | ACS580-01-017A-6 |
| ACS550-U1-022A-6 | ACS580-01-022A-6 |
| ACS550-U1-027A-6 | ACS580-01-027A-6 |
| ACS550-U1-032A-6 | ACS580-01-032A-6 |
| ACS550-U1-041A-6 | ACS580-01-041A-6 |
| ACS550-U1-052A-6 | ACS580-01-052A-6 |
| ACS550-U1-062A-6 | ACS580-01-062A-6 |
| ACS550-U1-077A-6 | ACS580-01-077A-6 |
| ACS550-U1-099A-6 | ACS580-01-099A-6 |
| ACS550-U1-125A-6 | ACS580-01-125A-6 |
| ACS550-U1-144A-6 | ACS580-01-144A-6 |
| ACS550 option | Function | ACS580 option |
|---|---|---|
| B055 | UL/NEMA Type 12 / IP54 | B056 — UL/NEMA Type 12 / IP55 |
| RCNA-01 | ControlNet | FCNA-01-KIT |
| RDNA-01 | DeviceNet | FDNA-01-KIT |
| RETA-01 | EtherNet/IP | FENA-21-KIT |
| RPBA-01 | PROFIBUS DP | FPBA-01 |
| OHDI-01 | 115/230 V digital input | CHDI-01 |
Do not assume an ACS550 option module can be physically transferred to ACS580. Confirm both hardware and communication compatibility before ordering.
If the existing ACS550 uses an encoder module, ABB's comparison guide directs the application to ACS880 because ACS580 does not provide an encoder card.
The original ACS550 may make sense when production must restart immediately and exact stock is available, wiring/PLC changes are undesirable, a validated legacy configuration must be preserved, or a short-term spare strategy is the priority. ACS580 migration may make sense when the equipment will remain in service long term, future lifecycle and spare support matter, control-system modifications are acceptable, or multiple ACS550 units are being standardized/modernized together.
For an ACS550 request, we can separately check: original ACS550 China-side availability; ABB's official migration path and the candidate ACS580 / ACS880 platform; migration risks across current, dimensions, fieldbus, options, wiring and application; and — where ABB compliance isn't mandatory and the application supports it — an alternative-brand option.
Full ACS550 type code / nameplate photo · motor nameplate photo · input voltage, motor current and application · existing fieldbus and option codes · cabinet and wiring photos · quantity and destination country · if available: electrical drawing, parameter backup and PLC model.
ABB — ACS550 to ACS580 Comparison Guide, Document 3AXD50000660681, ABB Library · ABB — ACS550 Legacy Drives, manufacturer lifecycle page, abb.com · ABB — ACS580 General Purpose Drives, manufacturer product page, abb.com. This page summarizes ABB's published migration guidance for sourcing purposes; it is not a reproduction of ABB's documentation.
Technical disclaimer: ElecBridge is an independent sourcing service and is not ABB. This page summarizes ABB's migration information for practical sourcing use and must not be presented as ABB engineering approval. Final drive selection, power-module sizing, wiring, fieldbus integration, parameterization and commissioning must be verified for the actual motor, machine and control system.